Navigation: Operator Control Panel (HMI) > HMI Main Screen > Data Input Page > Cam Data Page

Motor Cams

**User Level 3 is required for this feature**

**Changes made on this page will only affect the current downloaded product**

Scroll Prev Top Next More

Motor Cams

The motor cams should be altered on the Cam Data Page. The Slave Pos. row contains the data that will energize or not energize the motor. The Master Pos. row contains the master's position at each function of the motor.

 

Motor Master Pos. - Master's Position of each slave position.

Motor Slave Pos.

oVFD controlled - The number will be the device speed wanted in FPM

oMotor Starter controlled - 1 will energize and 0 will not energize

 

 

Example Cam in above screen - At point 1 the master position is 0 and the slave position is 0 which is not energized or if VFD controlled running at a speed of 0 FPM. Point 1 should always be master position 0 in order to know the motor's speed or status at the start of the cycle. At point 2 the master position is 5 and the slave position is 90 which is, if VFD controlled, running at a speed of 90 FPM. If the motor wasn't VFD controlled, then the slave position would be 1 which is energized. At point 3 the master position is 10 and the slave position is 0 which is not energized, or if VFD controlled, running at a speed of 0 FPM.