Vacuum Switch Setup

Previous topic Next topic Topic directory requires JavaScript JavaScript is required for expanding text JavaScript is required for the print function  

ZSE40 Vacuum Switch Setup:

 

1)In the Aagard wiring diagram, find the correct ON and OFF trigger values
2)Press and hold the SET button until a unit of measure is displayed (example KPa)
3)Use the UP and DOWN buttons to navigate until inH is displayed (inches of mercury)
4)Press and release the SET button; this will set inH as the unit of measure and the display should show a low number as the current reading
5)Press and release the SET button; the display should toggle between P_1 and a number
6)Use the arrow buttons to adjust the number of the ON trigger value (example -15.0)
7)Press and release the SET button; the display should toggle between P_2 and a number
8)Use the arrow buttons again to adjust the number of the OFF trigger value (example -12)
9)Press and release the SET button; the display will toggle between P_3 and a number
10) The default value is used for P_3; press/release the SET button to go to P_4
11) Again, the default value is used for P_4; press/release the SET button until the display is back to the main page, which should be showing a low number reading

 

The OUT 1 indicator should not be illuminated, and you are ready for production. The vacuum switch will provide an output when vacuum gets to the ON trigger value (example -15.0) and will not turn off the output unless the vacuum drops below the OFF trigger value (example -12.0).

 


 

ZSE40A Vacuum Switch Setup:

 

1)In the Aagard wiring diagram, find the correct P1 and H1 values
2)Press and hold the SET button until a function is displayed (example F 0)
3)Use the UP and DOWN buttons to navigate until Uni is displayed
a)Use the UP key to set display to inH (inches of mercury)
4)Press and release the SET button; this will set inH as the unit of measure and the display should show a low number as the current reading
5)From F 0, press the UP key once to navigate to F 1
a)Press the SET button 3 times so the display reads P_1
6)Use the UP and DOWN buttons to adjust the set point to what is stated on the wiring diagram
7)Press the SET button 1 more time so the display reads H_1
8)Use the UP and DOWN buttons to set the display to 3.0
9)Press SET button 2 times to return to F 1
10)Press and hold the SET button until the display is back to the main page; the main display should be showing a low number reading

 

The OUT 1 indicator should not be illuminated, and you are ready for production. The vacuum switch will provide an output when vacuum gets to the ON trigger value (example -15.0) and will not turn off the output unless the vacuum drops below the OFF trigger value (example -12.0).